Example finding · MDP-1, 400 A mainIR
ABC 61.4°C 6520
Phase A39.1°
Phase B61.4°
Phase C38.7°
ΔT 22.3 °C vs. similar phases: major discrepancy. Loose lug found and re-torqued the same week, then re-scanned under load.Illustrative example. Severity per NETA MTS Table 100.18 (>15 °C between similar components).
Problems we solve

Sound familiar?

Most calls start with one of these. Each one has a clear next step, and most can be handled without shutting your operation down.

Our insurer wants an annual infrared report.

We scan your gear under load and deliver a carrier-ready report with thermal images, photos and severity ratings, then fix what we find.

Infrared survey · Report · Repairs
We heard NFPA 70B is now required. Where do we start?

We build your Electrical Maintenance Program: equipment inventory, condition ratings, a test schedule and the records to prove it.

Maintenance program setup
Breakers trip and nobody knows why.

We log load and power quality, trace the circuit, and find whether it is overload, a failing breaker, harmonics or a ground fault.

Troubleshooting · Power quality study
We can’t afford a shutdown.

Infrared and ultrasound work on energized equipment. Hands-on maintenance is planned for nights, weekends or your scheduled outages.

Energized inspection · Outage planning
Our panels have no arc flash labels.

We coordinate the arc flash risk assessment, update the one-line diagram and install NFPA 70E labels so your team knows the hazard.

Arc flash assessment · Labeling
The generator hasn’t been load-tested in years.

We test the generator and transfer switch together and document results the way NFPA 110 and your inspector expect.

Generator & ATS testing
Our switchgear is decades old.

A condition assessment tells you what can be cleaned and torqued, what needs parts, and what to budget for replacement.

Condition assessment · Upgrade plan
Our energy bills keep climbing.

We find wasted load and propose LED retrofits, controls, and solar or EV charging sized to your facility.

Lighting & energy · Solar & EV
Services

Inspect. Maintain. Comply.

One licensed contractor for the whole cycle, from finding the problem to keeping the records.

Find problems early

Inspect & test

Before they become outages, fires or failed inspections.

  • Infrared thermographyThermal scans of energized gear for loose connections and overloads.
  • Visual & mechanical inspectionSwitchgear, panelboards, MCCs, disconnects and busway.
  • Insulation resistance testingFeeders, cables, motors and transformers.
  • Breaker & protective device testingTrip settings and operation verified.
  • Grounding & bonding testsGround resistance and continuity.
  • Power quality & load studiesHarmonics, imbalance and spare capacity.
Keep it running

Maintain & repair

Scheduled work that extends equipment life.

  • Switchgear & panel maintenanceCleaning, torque checks, re-termination.
  • Transformer maintenanceInspection, cleaning, connections and ventilation.
  • Motor & MCC serviceStarters, overloads, VFDs and controls.
  • Generator & transfer switch testingLoad testing and ATS operation per NFPA 110.
  • Emergency & exit lightingMonthly and annual tests documented per NFPA 101.
  • Troubleshooting & repairCorrective work on every deficiency we report.
Prove it

Plan & comply

The documentation and upgrades that keep you code-ready.

  • Electrical Maintenance ProgramNFPA 70B program, inventory and records.
  • Arc flash assessment & labelingRisk assessment and labels per NFPA 70E.
  • Single-line diagram updatesField-verified drawings of what is installed.
  • Short-circuit & coordination studiesEquipment ratings and selective tripping.
  • Lighting & energy upgradesLED retrofits and controls.
  • Solar & EV chargingDesign, installation and service.
Why OPS

Find it. Fix it. Document it.

Scan-only firms hand you a report and leave. Install-only contractors fix things but rarely test or document. You shouldn’t need both.

What you getScan-only firmInstall-only contractorOptimal Power Solutions
Finds hidden problems under loadYesRarelyYes
Repairs under the same licenseNoYesYes
NFPA 70B program and recordsReports onlyRarelyYes
Nights, weekends and planned outagesVariesVariesYes
Solar, battery and EV systemsRarelySomeYes
StandardSometimesUsually not
How it works

From walkthrough to a maintained facility

1

Walkthrough

We tour your electrical rooms, review existing records and agree on scope. No charge, no obligation.

2

Inspect & test

Infrared and visual inspection under load, plus any testing scoped for your gear.

3

Report

Findings ranked by risk, with thermal images, photos and a repair quote, within 3 business days.

4

Fix & maintain

We correct deficiencies, re-scan to verify, and schedule your next visits on a maintenance plan.

NFPA 70B · 2023 edition

Maintenance is now a standard

NFPA 70B moved from a recommended practice to a standard. It expects every facility to run a documented Electrical Maintenance Program, and insurers increasingly ask to see it.

≈48%

of facilities in an insurer’s five-year infrared program had serious or critical electrical faults, with an estimated $4 saved for every $1 spent.

Source: CNA results via Infrared Training Center
  • Written program

    A documented Electrical Maintenance Program with an equipment inventory and someone responsible for it.

  • Condition-based

    Each piece of equipment rated by its condition, which sets how often it must be maintained.

  • Every 12 months

    Infrared thermography of energized equipment at least once a year.

  • Every 5 years

    Arc flash risk assessment reviewed under NFPA 70E, and sooner after major changes.

  • Records

    Test results and corrective actions kept on file for insurers, inspectors and auditors.

Who we serve

Built for facilities that can’t go dark

Manufacturing plants Warehouses & distribution Commercial property Schools & municipal buildings Water & wastewater Healthcare & senior living Data & telecom rooms Sites with solar or EV charging
Questions

Before you call

Do you need to shut down our power?

Not for inspections. Infrared and ultrasound are done on energized equipment under normal load. Hands-on maintenance like cleaning and torquing needs an outage, and we schedule it for nights, weekends or your planned shutdowns.

Do you fix what you find?

Yes. Every report comes with a repair quote, and the work is done under a Massachusetts Master Electrician license. After repairs we re-scan to confirm the fix.

What does the report include?

Each finding gets a thermal image, a regular photo, the equipment location, the measured temperature rise, a severity rating and a recommended action. You get a PDF you can hand to your insurer or auditor.

How is pricing set?

After a free walkthrough. Price depends on the number of panels and pieces of equipment, access, and whether you want a one-time survey or an annual maintenance plan.

Our insurer already sends someone to scan. Why use you?

Insurer programs usually need a qualified electrician from your side to open energized panels, and they don’t make repairs. We can open the gear for them, or run the program ourselves and fix what turns up.

Where are you located?

We’re Central Mass based and work at commercial and industrial facilities across Massachusetts.

Get started

Book a facility walkthrough

Tell us about your facility and what’s on your mind. We’ll reply within one business day.

Call or text(774) 317-7378
Owner
Héctor Chamorro, Master Electrician

Prefer to talk? Call (774) 317-7378.